Power Losses Measurement Method for High Efficiency MV Oil-Insulated DC-DC Converter
Abstract
The concept of MVDC collection network for renewable applications requires a high efficiency DC-DC converter to connect the low voltage sources to the medium voltage network. The accurate measurement of low power losses is not possible with traditional electrical input-output power measurements. This paper adopts and extends a transient calorimetric method suited for the measurement on such converter. It is shown experimentally that this method can be applied to the measurement of the losses of an oil-immersed DC-DC converter. The maximum efficiency of the 83 kW, 1.2 to 6.6 kV prototype is measured at 99.16 ±0.035%.
Pierre Le Metayer, Cyril Buttay, Piotr Dworakowski, Drazen Dujic
Presented at PCIM 2025